Q: Inki kele kuvidisa kilo, inki ke nataka yau, mpe inki mutindu beto ke tesaka yau?
A: Kuvidisa kilo (P2) kele ngolo yina ke panzanaka na ba enroulement sambu na courant ya charge mpi flux stray, proportionnel na I2.
Bima ya kuvidisa kilo:
• I2R kuvidisa (~70–85% ya P6) - Kukangama ya DC Kuyoka ya Joule.
• Kuvidisa courant ya tourbillon na ba enroulement (~10–20%) - mpusu + effet ya pene-pene.
• Kuvidisa ya kukonda nzila na bitini ya ntungulu (~5–10%) - tanki, bapense, baboulon ya kati.
Mutindu ya kumeka - Nkufi-Kumeka ya Impedance ya Circuit:
|
Kitambi |
Kisalu |
Banoti |
|
1 |
Nkufi-circuit ya zole (na ndambu ya LV) |
Sadila barre ya nkufi ya ngolo- |
|
2 |
Sadila voltage ya kukulumuka na zulu ya ntete |
Yantika na zero; kumata na courant nominale |
|
3 |
Teza V2, I2=I_me pesa, P9 |
Vₖ is typically 5–15% of Uₙ |
|
4 |
Record Vₖ%=Vₖ / Uₙ × 100% |
Percentage ya voltage ya impedance |
|
5 |
P2 ya mbote tii na 75 degre |
Pₖ(75) = Pₖ(T) × (235+75)/(235+T) |
P2 ya kukonda kikalulu ke monisa:
• > +15% ya ba nsinga ya ngolo → ya ngolo-ya kukangama, bansinga ya kubukana, robinet ya mbi.
• Kukwenda na zulu → kuyedisa bangwisana ya kukonda ngolo, deformasio ya kukangama (ba tourbillons).
• V2% me soba > ±10% → mvingu ya bantu (ndilu ya IEC).
Kundimama: P6 Na nsi to kiteso mosi ti + 15% ya me ndimama na 75 degrés ; V2% na kati ya ±10% ya garanti.